Planet IECS-1116-DI – Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital Input

Planet
Availability:

Available on backorder


Model No – IECS-1116-DI

  • Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital Input
  • Built-in isolated 16 digital inputs
  • 2 x RJ45 bus interface
  • LED indicators for the input status
  • Removable terminal block connector
  • 9 ~ 48V DC wide input voltage range
  • Supports EtherCAT Distributed Clock (DC) mode and SyncManager mode
  • EtherCAT conformance test tool verified

 

Powering the Digital Transformation with EtherCAT

PLANET IECS-1116-DI is an industrial EtherCAT slave I/O module equipped with the EtherCAT protocol for today’s distributed industrial applications. The IECS-1116-DI provides high-density digital input channels and is protected with 3750 V DC isolation. Its compact size and DIN-rail mounting make installation in a cabinet easy. Pluggable terminal blocks and LED indicator help users to maintain and set up their system.

Flexible Installation

The IECS-1116-DI is an ideal high-speed distributed system solution which provides quick installation, real-time connection status monitoring, and wide-ranging power input and operating temperature to improve work efficiency, making them suitable for the harsh environment. Besides, the module comes with 2 10/100BASE-TX RJ45 ports. Through the EtherCAT technology, a network of up to 65,535 devices can be supported without the limitation of the type of topology — line, bus, tree, star or any arrangement – -being used.

Synchronization

An EtherCAT slave is an electronic device that carries out cyclical sequences of calculations and/or data copying tasks at a certain interval (cycle). The EtherCAT slave working cycle (e.g. in the range of a few µs up to several ms) can be derived from different sources. EtherCAT node can measure time difference between leaving and returning frame. With distributed clocks, EtherCAT can realize a precise synchronization time of <1us between each slave module.

Convenient and Reliable Power System 

The IECS-1116-DI is equipped with one 3-pin DC power input connector with screws for power supply installation. With power magnetic protection design, it can avoid the device burnout due to wrong wiring. In addition, it also possesses an integrated power supply source with wide-ranging voltages (9 to 48V DC) for worldwide high availability applications.

Environmentally Hardened Design

With the IP40 metal industrial case, the IECS-1116-DI provides a high level of immunity against electromagnetic interference and heavy electrical surges which are usually found on plant floors or in curb-side traffic control cabinets without air conditioning. It features a ventilated construction in which a cooling fan is not necessary, thereby making its operation noiseless. Being able to operate under the temperature range from -40 to 75 degrees C, the IECS-1116-DI can be placed in almost any difficult environment.

SKU: IECS-1116-DI Categories: , , ,
Digital Input
Channels 16
Input Type Wet (sink/source) / Dry (source)
Wet Contact On Voltage Level
3.5~50VOFF Voltage Level
4V max.
Dry Contact ON Voltage Level
Close to GNDOFF Voltage Level
Open
Photo Isolation 3750 VDC
Communication Interface
Connector 2 x RJ45
Protocol EtherCAT
Distance between Stations Max. 100m (100BASE-TX)
Data Transfer Medium Ethernet/EtherCAT cable (min. cat5), shielded
Power
Input Voltage Range 9~48V DC
Power Consumption 4W max.
Mechanical
Dimensions (W x D x H) 32 x 87 x 135mm
Installation DIN-rail and wall mounting
Case Material IP40 metal
Environment
Operating Temperature -40~75 degrees C
Storage Temperature -40~75 degrees C
Relative Humidity 5~95% (non-condensing)

Based on 0 reviews

0.0 overall
0
0
0
0
0

Only logged in customers who have purchased this product may leave a review.

There are no reviews yet.

Do you have a question?

Drop us a line by compiling the form below. We will be more than happy to reply to any of your questions!










    Please prove you are human by selecting the flag.

    Planet IECS-1116-DI Datasheet

    Download

    You may also like…